Please note: image may differ from actual product. See description for full details.
| List Price: |
$649.00 |
| Price: |
$549.49 |
| You Save: |
$99.51 (15%) |
|
In Stock
|
Overview
- Approvals:UL listed, CSA certified, FCC Class B compliance,
Novell Labs approved
- Input line: 6 ft. attached
- Output receptacles: (NEMA 5-15R) 4
- Maximum Dimensions: (HxWxD) 6.2x5.4x14.1
- Net Weight:29 lbs.
- Shipping Weight: 32 lbs
- Nominal Input voltage: 120 Vac, single phase; 50 or 60 Hz
(auto-selectable)
- Transfer time :(typical/max) 2/4 milliseconds, includes
detection time
- On-Battery Output voltage: Pure sine wave output at 115 Vac
+/-5%, -10% after low battery warning, synchronized to utility
line
- Smart Boost and Smart Trim Operation: On-Line operation for
input between 90 to 145 Vac. Output will be 103 to 132 VAC.
SmartBoost increases voltage 12% if input is 90 to 103 Vac.
SmartTrim reduces voltage 12% below input if 145 to 132 Vac.
- Double Pole Circuit breaker/Double Pole Switch: Safety reasons
dictate that the Delta Power shipboard Smart-UPS have a double pole
circuit breaker and a double pole switch since both legs carry
power.
- Capacity (Volt-Amps, Watts): 700,450
- Load power factor range, crest factor range: 0.5 to 1.0,
<5
- Surge energy rating, peak current: capability 320 Joules,
26kA
- Normal, common mode clamping response time:0 ns, <5 ns
typical
- Normal mode surge voltage let through when subjected to IEEE
587 Cat. A 6kV test: <0.7% of peak typical
- Normal/common mode noise suppression at 1.0MHz, 3.0MHz,
10.0MHz: 68/50, 57/50, 50/27 dB
- Sealed, maintenance-free lead acid batteries with 3-6 year
typical lifetime: Two 12V, 6.5AH
- Recharge time to 90% capacity after discharge into 50% load: 1
to 2 hours
- Ambient operation: 10,000 ft. (3,000 meters) max. elevation,
0-95% humidity non-condensing, 32-113 deg F (0-40 deg C)
|